Monday, August 17, 2015

Allen Bradley plc analog scaling

SCL INSTRUCTION


FOR ANALOG INPUT:-

In case of Micrologix -1000 A for current signal (4 to 20 mA),

Max Value for i/p = 31230 (Approx.)

So min value at 4 mA = 31230*4/20 = 6246 (Approx.)

Let the range of RTD is 0 to 400 degree C.

To calculate the value of rate & offset please use following formula.

1). Rate = (scaled max. - scaled min.) * 10000 / (input max. - input min.)
           
               = (400 – 0) * 10000 / (31230-6246)

     Rate = 160

2). Offset = scaled minimum - (input minimum x rate)

                 = 0 – (6246 * .0160)
      Offset = -100








FOR ANALOG OUTPUT

In case of Micrologix -1000 A for current signal (4 to 20 mA),

To use the AI double click on I/O Configuration & then I/O Setup.
Select the o/p mode (may be current or voltage, which you want to use).

If you want to provide 0 to 10 V signal on o/p then the value at O:0.4 should be 0 to 31230 (Approx.).




Remote IOS of Allen-Bradley

change the ip address of local and remote IOS of Allen-Bradley
start stop logic in rs logix 5000 by using emote IOS of Allen-Bradley

Allen-Bradley plc remote ios communication with intouch ad rs view scada




Allen-Bradley compact logic 1769  BY using Ethernet adopter             
connected to remote ios and communication to Review32 and             
 Intouch scada



Saturday, August 15, 2015

abb positioner (tzidc) for control valve calibration procedure







Abb positioner manual checking and opening of control valve:






A.Press Mode key  for 3 sec untill parameter


1.3 MAN_SENS
then release the  Mode key



B.now showing SENS_POS  which is -25 degree or any other reading.this is zero or 0 % close  postion of the control valve.




C.For 100% opening press both keys: 1st up errow  key with 2nd  errow dowen key  untill valve not open 100 %.then release the both key.




Note: alwayes keep the control valve at zero position befor exit SENS_POS parameter.




Abb positioner Auto caliberation of control valve:



A.Press Mode key for 5 sec untill parameter

ADJ_LIN
3
2
1
0
then release the Mode key


B.auto caliberation working 10 to 100 % Run

c. end of caliberation .