Sunday, July 11, 2010

Control Loop Hardware and Troubleshooting

Chapter

Control Loop Hardware and Troubleshooting

Overall Course Objectives

           Develop the skills necessary to function as an industrial process control engineer.

      Skills

       Tuning loops

       Control loop design

       Control loop troubleshooting

       Command of the terminology

      Fundamental understanding

       Process dynamics

       Feedback control

Control Relevant Aspects of Control Loop Hardware

           Necessary for control loop troubleshooting:

      To determine if each subsystem (control computer, actuator system, and sensor system) is functioning properly

      To understand the proper design and operation of all the components that make-up each of the subsystems of a control loop

Control Diagram of a Typical Control Loop

Components and Signals of a Typical Control Loop

Controllers/Control Computers

           Pneumatic controllers

           Electronic analog controllers

           Supervisory control computers

           Distributed Control Systems (DCS)

           Fieldbus technology

Pneumatic Controllers - Phase I

           Introduced in the 1920’s

           Installed in the field next to the valve

           Use bellows, baffles, and nozzles with an air supply to implement PID action.

           Provided automatic control and replaced manual control for many loops

Pneumatic Controllers - Phase II

           Transmitter type pneumatic controllers began to replace field mounted controllers in the late 1930’s.

           Controller located in control room with pneumatic transmission from sensors to control room and back to the valve.

           Allowed operators to address a number of controllers from a centralized control room.

Pneumatic Controller Installation

  Electronic Analog Controllers

           Became available in the late 1950’s.

           Replaced the pneumatic tubing with wires.

           Used resistors, capacitors, and transistors based amplifiers to implement PID action.

           Out sold pneumatic controllers by 1970.

           Allowed for advanced PID control: ratio, feedforward, etc.

Electronic Controller Installation

     Computer Control System

           Based upon a mainframe digital computer.

           Offered the ability to use data storage and retrieval, alarm functions, and process optimization.

           First installed on a refinery in 1959.

           Had reliability limitations.

  Supervisory Control Computer

Distributed Control System- DCS

           Introduced in the late 1970’s.

           Based upon redundant microprocessors for performing control functions for a part of the plant.      SUPERIOR RELIABILITY

           Less expensive per loop for large plants.

           Less expensive to expand.

           Facilitates the use of advanced control.

DCS Architecture

DCS and Troubleshooting

           The data storage and trending capability of a DCS greatly facilitate troubleshooting control problems.  That is, the sources of process upsets can many times be tracked down through the process by trending a group of process measurements until the source of the process upset is located.

Control Relevant Aspects of a DCS

           The most important control aspect of a DCS is the cycle time for controller calls.  The shortest cycles times are typically around 0.2 seconds while  most loops can be executed every 0.5 to 1.0 seconds.  These cycle times affect flow control loops and other fast control loops.

PLCs

           PLCs can withstand has industrial enviroments.

           PLCs are used for discrete and continuous control.

           Discrete control is used for startup and shutdown and batch sequencing operations.

           Ladder logic is used to program PLCs.

PLCs vs. DCSs

           Advantage of PLCs:

      Better to withstand harsh operating enviroments, faster cycle time are possible, easier to maintain due to modular nature and lower cost for small and medium sized applications.

           Advantage of DCSs:

      Lower cost per loop for applications involving a large number of control loops.

PLC Architecture

          Fieldbus Technology

           Based upon smart valves, smart sensors and controllers installed in the field.

           Uses data highway to replace wires from sensor to DCS and to the control valves.

           Less expensive installations and better reliability.

           Can mix different sources (vendors) of sensors, transmitters, and control valves.

           Now commercially available and should begin to replace DCSs.

 

Fieldbus Architecture

Actuator System

           Control Valve

      Valve body

      Valve actuator

           I/P converter

           Instrument air system

Typical Globe Control Valve

Cross-section of a Globe Valve

Types of Globe Valves

           Quick Opening- used for safety by-pass applications where quick opening is desired

           Equal Percentage- used for about 90% of control valve applications since it results in the most linear installed characteristics

           Linear- used when a relatively constant pressure drop is maintained across the valve

Inherent Valve Characteristics

Use of the Valve Flow Equation

Typical Flow System

Pressure Drop vs. Flow Rate

Installed Flow Characteristic

Slope of Installed Characteristic

Effect of Linearity in the Installed Valve Characteristics

           Highly nonlinear installed characteristics can lead to unstable flow control or a sluggish performance for the flow controller.

Flow System with Relatively Constant Valve Pressure Drop

Pressure Drop vs. Flow Rate

Installed Valve Characteristics

Analysis of These Examples

           Note the linear installed valve characteristics over a wide range of stem positions.

           If the ratio of pressure drop across the control valve for the lowest flow rate to the value for the highest flow rate is greater than 5, an equal percentage control valve is recommended.

Control Valve Design Procedure

            Evaluate Cv at the maximum and minimum flow rate using the flow equation for a valve (Eq 2.3.3).

            Determine which valves can effectively provide the max and min flow rate remembering that, in general, the valve position should be greater than about 15% open for the minimum flow rate and less than 85% open for the maximum flow rate.

            Choose the smallest valve that meets the above criterion for the minimum capital investment or choose the largest valve to allow for future throughput expansion.

Additional Information Required to Size a Control Valve

           CV versus % open for different valve sizes.

           Available pressure drop across the valve versus flow rate for each valve.  Note that the effect of flow on the upstream and downstream pressure must be known.

Valve Sizing Example

           Size a control valve for max 150 GPM of water and min of 50 GPM.

Determine CV at Max and Min FV

              Use the valve flow equation (Equation 2.3.3) to calculate Cv

            For DP, use pressure drop versus flow rate      (e.g., Table on page 82)

Valve Position for Max and Min Flows for Different Sized Valves

Analysis of Results

           2-inch valve appears to be best overall choice:  least expensive capital and it can provide up to a 50% increase in throughput.

           3-inch and 4-inch valve will work, but not recommended because they will cost more to purchase.  The 2-inch valve will provide more than enough extra capacity (i.e., something else will limit capacity for it)

Valve Deadband

           It is the maximum change in instrument air pressure to a valve that does not cause a change in the flow rate through the valve.

           Deadband determines the degree of precision that a control valve or flow controller can provide.

           Deadband is primarily affected by the friction between the valve stem and the packing.

For Large Diameter Lines (>6”), Use a Butterfly Valve

Valve Actuator Selection

           Choose an air-to-open for applications for which it is desired to have the valve fail closed.

           Choose an air-to-close for applications for which it is desired to have the valve fail open.

Cross-section of a Globe Valve

Optional Equipment

           Valve positioner- a controller that adjusts the instrument air in order to maintain the stem position at the specified position.  Greatly reduces the deadband of the valve.  Positioners are almost always used on valves serviced by a DCS.

           Booster relay- provides high capacity air flow to the actuator of a valve.  Can significantly increase the speed of large valves.

Photo of a Valve Positioner

Adjustable Speed Pumps

           Used extensively in the bio-processing industries (better to maintain sterile conditions and relatively low flow rates).

           Fast and precise.

           Do require an instrument air system (i.e., 4-20 mA signal goes directly to pump).

           Much higher capital costs than control valves for large flow rate applications.

Control Relevant Aspects of Actuator Systems

           The key factors are the deadband of the actuator and the dynamic response as indicated by the time constant of the valve.

           Control valve by itself- deadband 10-25% and a time constant of 3-15 seconds.

           Control valve with a valve positioner or in a flow control loop- deadband 0.1-0.5% and a time constant of 0.5-2 seconds.

Chapter

Control Loop Hardware and Troubleshooting

Overall Course Objectives

           Develop the skills necessary to function as an industrial process control engineer.

      Skills

       Tuning loops

       Control loop design

       Control loop troubleshooting

       Command of the terminology

      Fundamental understanding

       Process dynamics

       Feedback control

Control Relevant Aspects of Control Loop Hardware

           Necessary for control loop troubleshooting:

      To determine if each subsystem (control computer, actuator system, and sensor system) is functioning properly

      To understand the proper design and operation of all the components that make-up each of the subsystems of a control loop

Control Diagram of a Typical Control Loop

Components and Signals of a Typical Control Loop

Controllers/Control Computers

           Pneumatic controllers

           Electronic analog controllers

           Supervisory control computers

           Distributed Control Systems (DCS)

           Fieldbus technology

Pneumatic Controllers - Phase I

           Introduced in the 1920’s

           Installed in the field next to the valve

           Use bellows, baffles, and nozzles with an air supply to implement PID action.

           Provided automatic control and replaced manual control for many loops

Pneumatic Controllers - Phase II

           Transmitter type pneumatic controllers began to replace field mounted controllers in the late 1930’s.

           Controller located in control room with pneumatic transmission from sensors to control room and back to the valve.

           Allowed operators to address a number of controllers from a centralized control room.

Pneumatic Controller Installation

  Electronic Analog Controllers

           Became available in the late 1950’s.

           Replaced the pneumatic tubing with wires.

           Used resistors, capacitors, and transistors based amplifiers to implement PID action.

           Out sold pneumatic controllers by 1970.

           Allowed for advanced PID control: ratio, feedforward, etc.

Electronic Controller Installation

     Computer Control System

           Based upon a mainframe digital computer.

           Offered the ability to use data storage and retrieval, alarm functions, and process optimization.

           First installed on a refinery in 1959.

           Had reliability limitations.

  Supervisory Control Computer

Distributed Control System- DCS

           Introduced in the late 1970’s.

           Based upon redundant microprocessors for performing control functions for a part of the plant.      SUPERIOR RELIABILITY

           Less expensive per loop for large plants.

           Less expensive to expand.

           Facilitates the use of advanced control.

DCS Architecture

DCS and Troubleshooting

           The data storage and trending capability of a DCS greatly facilitate troubleshooting control problems.  That is, the sources of process upsets can many times be tracked down through the process by trending a group of process measurements until the source of the process upset is located.

Control Relevant Aspects of a DCS

           The most important control aspect of a DCS is the cycle time for controller calls.  The shortest cycles times are typically around 0.2 seconds while  most loops can be executed every 0.5 to 1.0 seconds.  These cycle times affect flow control loops and other fast control loops.

PLCs

           PLCs can withstand has industrial enviroments.

           PLCs are used for discrete and continuous control.

           Discrete control is used for startup and shutdown and batch sequencing operations.

           Ladder logic is used to program PLCs.

PLCs vs. DCSs

           Advantage of PLCs:

      Better to withstand harsh operating enviroments, faster cycle time are possible, easier to maintain due to modular nature and lower cost for small and medium sized applications.

           Advantage of DCSs:

      Lower cost per loop for applications involving a large number of control loops.

PLC Architecture

          Fieldbus Technology

           Based upon smart valves, smart sensors and controllers installed in the field.

           Uses data highway to replace wires from sensor to DCS and to the control valves.

           Less expensive installations and better reliability.

           Can mix different sources (vendors) of sensors, transmitters, and control valves.

           Now commercially available and should begin to replace DCSs.

 

Fieldbus Architecture

Actuator System

           Control Valve

      Valve body

      Valve actuator

           I/P converter

           Instrument air system

Typical Globe Control Valve

Cross-section of a Globe Valve

Types of Globe Valves

           Quick Opening- used for safety by-pass applications where quick opening is desired

           Equal Percentage- used for about 90% of control valve applications since it results in the most linear installed characteristics

           Linear- used when a relatively constant pressure drop is maintained across the valve

Inherent Valve Characteristics

Use of the Valve Flow Equation

Typical Flow System

Pressure Drop vs. Flow Rate

Installed Flow Characteristic

Slope of Installed Characteristic

Effect of Linearity in the Installed Valve Characteristics

           Highly nonlinear installed characteristics can lead to unstable flow control or a sluggish performance for the flow controller.

Flow System with Relatively Constant Valve Pressure Drop

Pressure Drop vs. Flow Rate

Installed Valve Characteristics

Analysis of These Examples

           Note the linear installed valve characteristics over a wide range of stem positions.

           If the ratio of pressure drop across the control valve for the lowest flow rate to the value for the highest flow rate is greater than 5, an equal percentage control valve is recommended.

Control Valve Design Procedure

            Evaluate Cv at the maximum and minimum flow rate using the flow equation for a valve (Eq 2.3.3).

            Determine which valves can effectively provide the max and min flow rate remembering that, in general, the valve position should be greater than about 15% open for the minimum flow rate and less than 85% open for the maximum flow rate.

            Choose the smallest valve that meets the above criterion for the minimum capital investment or choose the largest valve to allow for future throughput expansion.

Additional Information Required to Size a Control Valve

           CV versus % open for different valve sizes.

           Available pressure drop across the valve versus flow rate for each valve.  Note that the effect of flow on the upstream and downstream pressure must be known.

Valve Sizing Example

           Size a control valve for max 150 GPM of water and min of 50 GPM.

Determine CV at Max and Min FV

              Use the valve flow equation (Equation 2.3.3) to calculate Cv

            For DP, use pressure drop versus flow rate      (e.g., Table on page 82)

Valve Position for Max and Min Flows for Different Sized Valves

Analysis of Results

           2-inch valve appears to be best overall choice:  least expensive capital and it can provide up to a 50% increase in throughput.

           3-inch and 4-inch valve will work, but not recommended because they will cost more to purchase.  The 2-inch valve will provide more than enough extra capacity (i.e., something else will limit capacity for it)

Valve Deadband

           It is the maximum change in instrument air pressure to a valve that does not cause a change in the flow rate through the valve.

           Deadband determines the degree of precision that a control valve or flow controller can provide.

           Deadband is primarily affected by the friction between the valve stem and the packing.

For Large Diameter Lines (>6”), Use a Butterfly Valve

Valve Actuator Selection

           Choose an air-to-open for applications for which it is desired to have the valve fail closed.

           Choose an air-to-close for applications for which it is desired to have the valve fail open.

Cross-section of a Globe Valve

Optional Equipment

           Valve positioner- a controller that adjusts the instrument air in order to maintain the stem position at the specified position.  Greatly reduces the deadband of the valve.  Positioners are almost always used on valves serviced by a DCS.

           Booster relay- provides high capacity air flow to the actuator of a valve.  Can significantly increase the speed of large valves.

Photo of a Valve Positioner

Adjustable Speed Pumps

           Used extensively in the bio-processing industries (better to maintain sterile conditions and relatively low flow rates).

           Fast and precise.

           Do require an instrument air system (i.e., 4-20 mA signal goes directly to pump).

           Much higher capital costs than control valves for large flow rate applications.

Control Relevant Aspects of Actuator Systems

           The key factors are the deadband of the actuator and the dynamic response as indicated by the time constant of the valve.

           Control valve by itself- deadband 10-25% and a time constant of 3-15 seconds.


           Control valve with a valve positioner or in a flow control loop- deadband 0.1-0.5% and a time constant of 0.5-2 seconds.

Thursday, July 8, 2010

Wednesday, July 7, 2010

EPLAN_Electric_P8_1.9.5






Electrical computer-aided design as the vanguard of the times, since 1984, EPLAN has been planning for the electrical, engineering and project management in the field to provide intelligent software solutions and professional services to global enterprises mark. EPLA N Cabinet, EPLAN product family is not only the leadership of the global market, has now become the industry standard electrical design of the world’s family of CAE software, but also to the electrical control cabinet for 3D design EPLA N Cabinet, for fluid EPLAN Fluid Engineering and Process industries such as EPLAN PPE Products.
source by:http://www.eplan.in/en/solutions/electrical-engineering/eplan-electric-p8/

book series plc

Mitsubishi FX Programmable Logic Controllers, 2 Ed: Applications and Programming

 

source by:http://www.mitsubishielectric.asia/india/products/automation/

Tuesday, July 6, 2010

Siemens PCS 7.0

SOURCE BY:http://www.siemens.com/entry/cc/en/#product/189260

RS Emulate 5000 V. 17








source by:http://www.rockwellautomation.com/global/support/downloads.page?

FactoryTalk RSView Machine Edition 5.0 CPR 8


source by:http://www.rockwellautomation.com/rockwellsoftware/support/software-downloads.page?

RSLinx




source by:http://www.rockwellautomation.com/rockwellsoftware/support/software-downloads.page?
---------------------------

Serial port Emulator, Serial port Monitor, Virtual Serial Port

----------------------------------------------------
source by: http://www.eltima.com/products/
- Serial port Monitoring  http://www.eltima.com/download/serial_port_monitor.exe
- Serial port Emulator
- Virtual serial port  http://www.eltima.com/download/vspd.exe
- Serial port splitter  http://www.eltima.com/download/serial_splitter.exe
- Serial port terminal  http://www.eltima.com/download/serial_port_terminal.exe
- Serial port over ethernet  http://www.eltima.com/download/serial_ethernet_connector.exe
- Serial RS232 data logger  http://www.eltima.com/download/rs232_data_logger.exe

-------------------------------------